 Super Power Meter 1000

Description
All electronic, microprocessor controlled,
digital watthour/demand meter providing all essential
features and information for on-site/remote tenant
reading and billing and/or energy monitoring
applications, and much more.
Technical Specifications
Accuracy
ANSI C12.16 Electronic Meter Standards
Power Input
Types:
2-wire or 3-wire single phase
3-phase, 4-wire WYE
3-phase, 3-wire DELTA
Voltages: 120V, 240V,
120/240V
120/208V, 277/480V
Frequency: 60Hz
(other configurations available, please inquire)
Operating Ranges
Voltage:
+/- 20% of rated voltage
Current:
5A secondary
Frequency: 57Hz to 63Hz
Temperature: -40 C to +85 C
Humidity: 0 to 95%
non-condensing
Non-Volatile Memory
24k ROM, 1k EEPROM, 32k RAM
Data is stored and secured in the event of a power
failure for a minimum of 6 months
Liquid Crystal Display
Preprogrammed at factory to display automatically and
sequentially every 5 seconds: kWh, kW (15 or 30 minute
integration interval). Additional programmable
display: meter #, serial #, location code, voltage per
phase, current per phase, gas usage, water usage,
time-of-day output, temperature, wind speed, water level.
30 Day History
Factory programmed to store 30 day daily kW and kWh
history in non-volatile memory
Time-Of-Day Recording
Up to 3 time periods (user programmable)
Digital Input
1 inputs 0-5V, plus/negative logic acceptable,
opto-isolated
Analog Input
3 inputs 0-5V, 10k-ohm input impedance
Relay Controlled Output
SPST switch, 1A/125VAC
Installation
Potential Wire Type/Sizes: 14
to 18 gauge, solid or stranded
Data
Cable:
22 gauge, 4 conductor
Current Transformer Wire: 14 to
20 gauge
Enclosure
9 x 6 x 3 surface mount, steel,
lockable, hinged
Other Outstanding Features
Field Programmable, kW reset button, kW/kWh reset
button, RS-232 communications, RS-422 communications,
password protected, spike and surge protected, fuse
protected circuitry, real time clock.
Note: Specifications are subject to
change without notice due to circumstances and
availability of materials beyond our control.
However, basic specifications regarding operation and
accuracy will be maintained at all times.
For pricing and availability, please
call or e-mail us.

|