Description
An all electronic, microprocessor controlled, digital watthour/demand meter for
monitoring the load performance of transformers located on utility poles and in sub-surface vaults.

Technical Specifications

Accuracy
ANSI C12.16 Electronic Meter Standards, +/- 0.5% full scale

Power Input
Types:          2-wire or 3-wire single phase
                    3-phase, 4-wire WYE
                    3-phase, 3-wire DELTA
Voltages:      120V, 240V, 120/240V
                    120/208V, 277/480V
Frequency:   60Hz
(other configurations available, please inquire)

Operating Ranges
Voltage:           +/- 20% of rated voltage
Current:           5A secondary
Frequency:      57Hz to 63Hz
Temperature:  -40 C to +85 C
Humidity:        0 to 95% non-condensing

Non-Volatile Memory
32k ROM, 512 bytes EEPROM, 32k RAM
Data is stored and secured in the event of a power failure for a minimum of 3 years

Liquid Crystal Display
Preprogrammed at factory to display automatically and sequentially every 5 seconds:
Meter Number, Location Code Date, Time, voltage per phase, kWh, kW (15 or 30 minute integration interval), ambient temperature, transformer temperature, wind speed.
Additional programmable display: serial #, current per phase, instantaneous kW per phase, water level.

30 Day Daily History
Factory programmed to record and store 30 day daily kW and kWh history in   non-volatile memory

60 Day Hourly History
Factory programmed to record and store hourly kWh, kW, voltage and current per phase, 2 temperatures, wind speed, for the past 60 days

Event Log Reporting
Factory programmed to record the following events with date/time and maintain the 20 latest occurrences of each in non-volatile memory:

                  Voltage exceeds or drops below parameters
                  Change in voltage exceeds a parameter
                  Instantaneous kW exceeds a parameter
                  Temperature exceeds or drops below parameters
                  Wind speed exceeds a parameter
                  Water level exceeds a parameter

All parameters are user definable and configurable.

Time-Of-Day Recording
Up to 3 time periods (user programmable)

Digital Input
3 inputs 0-5V, plus/negative logic acceptable, opto-isolated

Analog Input
2 input 0-5V, 10k-ohm input impedance

Relay Controlled Output
SPST switch, 1A/125VAC

TELCO Communications
1200 baud modem built-in, FCC Part 68 registered DAA, Bell 212A/103 and CCITT V.22 standards, ‘AT’ command set compatible, automatic answer, speed, parity

Installation
Mounting:                              S-Base, A-Base (numerous configurations)
Potential Wire Type/Sizes:     14 to 18 gauge, solid or stranded
Data Cable:                           22 gauge, 4 conductor
Current Transformer Wire:     14 to 20 gauge

Enclosure
12” x 10” x 5” surface mount, steel, lockable, hinged, NEMA/EEMAC Type 12 and Type 13 (Type 3 and Type 4 also available), UL 50 Type 12 and Type 13, JIC standard EGP-I-1967, CSA Type 12, IEC 529, IP65

Other Outstanding Features
Field Programmable, kW reset button, kW/kWh reset button, RS-232 communications, RS-422 communications, RF and Cellular Phone communications expandable, password protected, spike and surge protected, fuse protected circuitry, real time clock.

Note: Specifications are subject to change without notice due to circumstances and availability of materials beyond our control. However, basic specifications regarding operation and accuracy will be maintained at all times.